Max. switching characteristics (acc. to DIN EN 60947-5-1 table C2):
AC 15:
230V/3A
DC13:
24V/4A
UL508:
C300
Maximal contact load at
AC 1 with 230V:
2 contacts each with 6A
Gold contacts with 4-6µm layer thickness
When high voltages and currents are switched, the layer of gold is destroyed already after a few switching operations.
Once the gold layer is damaged due to the switching of high loads, such a contact must not be used any more for signal and control current circuits.
Safe contact making is then only possible at high loads with the formation of sparks.
Load limit curve with direct current
1)
Inductive load, L/R 40 ms
2)
Resistive load
Excitation voltage range
1)
Max. excitation voltage with contact load
< 2A
2)
Min. excitation voltage (guaranteed values) without previous operation
No heat accumulation due to intrinsic heating of other components.