PCB relay with forcibly guided contacts |
| - |
Protective separation between coil and contacts (leakage and creepage distances
> 14mm); protective separation between left and right contact side (leakage and creeping distances > 5.5mm) |
| - |
EN 50205 type A |
| - |
Contact mounting:
SIM312 3NO/1NC
SIM222 2NO/2NC |
| - |
Small external dimensions |
| - |
Mean coil power 1W |
| - |
Holding power 0.23W |
|
|
 |
| |
|
|
|
| |
Standard coils for direct current (other voltages on request)
|
|
|
|
|
| |
|
|
|
| |
Nominal
voltage VDC |
Min. pick-up
voltage at 20°C |
Drop-out
voltage at 20 °C |
Nominal
current in mA |
Resistance
in Ohm at 20 °C |
Tolerance
in % |
| 5 |
3,75 |
> 0,5 |
181,8 |
27,5 |
± 10 |
| 6 |
4,5 |
> 0,6 |
166,0 |
36 |
± 10 |
| 12 |
9,0 |
> 1,2 |
85,7 |
140 |
± 10 |
| 21 |
15,75 |
> 2,1 |
46,6 |
450 |
± 10 |
| 24 |
18,0 |
> 2,4 |
40,0 |
600 |
± 10 |
| 48 |
36,0 |
> 4,8 |
20,8 |
2‘300 |
± 10 |
| 60 |
45,0 |
> 6,0 |
16,6 |
3‘600 |
± 13 |
| 110 |
82,5 |
> 11,0 |
9,6 |
12‘000 |
± 15 |
|
| |
|
|
|
| |
Ordering example
|
|
|
| |
|
|
|
| |
 |
|
|
| |
|
|
|