PCB relay with forcibly guided contacts |
| - |
Protective separation between coil/control
contacts and output contacts (> 10mm) and
output contacts side by side (> 8mm) |
| - |
EN 50205, type A |
| - |
Contact mounting:
SIR312 3NO/1NC
SIR222 2NO/2NC |
| - |
Small external dimensions |
| - |
Mean coil power 0.36W |
| - |
Holding power 0.12W |
| - |
For Railway Applications: EN 50155 |
|
|
 |
| |
|
|
|
| |
Standard coils for direct current (other voltages on request) |
|
|
|
|
|
|
|
|
| |
|
|
|
| |
Nominal
voltage VDC |
Min. pick-up
voltage at 20°C |
Drop-out
voltage at 20 °C |
Nominal
current in mA |
Resistance in Ohm at 20 C |
Tolerance
in % |
| 5 |
3,75 |
> 0,5 |
72,0 |
69,4 |
± 10 |
| 6 |
4,5 |
> 0,6 |
60,0 |
100 |
± 10 |
| 9 |
6,75 |
> 0,9 |
40,0 |
225 |
± 10 |
| 12 |
9,0 |
> 1,2 |
30,0 |
400 |
± 10 |
| 18 |
13,5 |
> 1,8 |
20,0 |
900 |
± 10 |
| 24 |
18,0 |
> 2,4 |
15,0 |
1'600 |
± 10 |
| 48 |
36,0 |
> 3,6 |
7,5 |
6'400 |
± 13 |
| 60 |
45,0 |
> 4,5 |
6,0 |
10'000 |
± 15 |
|
| |
|
|
|
| |
Ordering example |
|
|
|
|
| |
|
|
|
| |
 |
|
|
| |
|
|
|