PCB relay with forcibly guided contacts |
| - |
Protective separation between coil/control
contacts and output contacts (> 10mm) and
output contacts side by side (> 8mm) |
| - |
EN 50205, type A |
| - |
Contact mounting:
SIR312P „Power“ Control contacts 1NO/1NC
Output contacts 2NO
SIR222P „Power“ Control contacts 2NC
Output contacts 2NO |
| - |
Inrush current 60A / continuous current 12A |
| - |
Mean coil power 0.75W |
| - |
Holding power 0.23W |
|
|

 |
| |
|
|
|
| |
Standard coils for direct current (other voltages on request) |
|
|
|
|
|
|
|
|
| |
|
|
|
| |
Nominal
voltage VDC |
Min. pick-up
voltage at 20°C |
Drop-out
voltage at 20 °C |
Nominal
current in mA |
Resistance in Ohm at 20 C |
Tolerance
in % |
| 5 |
<3,5 |
> 0,5 |
151,0 |
33 |
± 10 |
| 12 |
<8,4 |
> 1,2 |
63,1 |
190 |
± 10 |
| 20 |
<14,0 |
> 2,0 |
37,7 |
530 |
± 10 |
| 18 |
<12,6 |
> 1,8 |
41,6 |
432 |
10 |
| 24 |
<16,8 |
> 2,4 |
31,5 |
760 |
± 10 |
| 48 |
<33,6 |
> 4,8 |
15,7 |
3‘050 |
± 10 |
| 60 |
<42,0 |
> 6,0 |
12,5 |
4‘800 |
± 10 |
| 110 |
<77,0 |
> 11,0 |
6,8 |
16‘000 |
± 15 |
|
| |
|
|
|
| |
Ordering example |
|
|
|
|
| |
|
|
|
| |
 |
|
|
| |
|
|
|